Zone-Selective Interlocking

For Georgia engineers, contractors and facility teams, zone-selective interlocking (ZSI) can limit the delay imposed on an upstream breaker when a downstream fault occurs. Its value depends on compatible protective devices, correct signal paths and coordinated settings. This guide explains what to define for a new switchboard and what to verify before equipment is released for construction.

Made in USAUL 891 switchboard assemblies — low voltage onlyAccelerated lead times — confirm availability
Project-specific

Define the application and requirements.

Built in the USA

Discuss equipment and assembly options.

Schedule-aware

Confirm lead times for your order.

How the interlocking signal changes a trip

In a coordinated system, an upstream protective device may use intentional time delay to let a downstream device clear a fault first. That delay helps preserve service to unaffected parts of the system, but it can leave the fault in place longer when the fault is within the upstream device’s own zone. ZSI adds a communication signal between compatible devices to distinguish those conditions.

When a downstream device detects a fault within its protected zone, it sends a restraint signal upstream. The upstream device then follows the coordinated delay. If the upstream device detects a fault and receives no restraint signal from a downstream device, it can operate on its shorter ZSI response, subject to its programmed settings and manufacturer instructions. ZSI changes the response for defined conditions; it does not replace coordination studies or protection engineering.

Define zones and device compatibility

Before specifying ZSI, identify which breakers are intended to communicate and what each one protects. A one-line diagram should show the source, bus sections, feeder breakers, tie breakers and downstream devices that form the proposed zones. The engineer can then define where restraint signals originate, which upstream devices receive them and how the system should behave for faults at each location.

Compatibility is specific to the protective trip units, accessories, signal interfaces and wiring method. Breakers that appear similar may not support the same function or signal scheme. Confirm device models and options with applicable manufacturer documentation, including whether the intended protection elements participate in ZSI and whether the arrangement supports the desired direction of coordination. Do not assume that adding a wire between breakers creates a valid interlocking scheme.

Settings, wiring and failure behavior

The protection study should establish pickup values, time delays, short-time and ground-fault functions where applicable, and the intended coordination outcomes. ZSI should be assessed alongside available fault-current information and the selected devices’ interrupting and withstand capabilities. An engineer must evaluate the actual system and applicable requirements; a switchboard configuration alone cannot establish a safe or compliant design.

The design also needs a defined signal circuit, terminal assignments, routing and interface details. Ask how the devices indicate restraint, how the signal is supervised or checked, and what the manufacturer specifies if a signal wire is open, shorted or misconnected. Failure behavior matters because a lost restraint signal may change an upstream device’s response. Document intended operation, testing methods and any limitations so commissioning personnel can verify the installed scheme against approved settings.

Information to settle before the build

For a manufacturer quote, provide the one-line diagram, system voltage and frequency, source and transformer data, available fault-current information, bus arrangement, feeder schedule and required protective-device functions. Include proposed breaker and trip-unit selections if already engineered, plus the coordination study or its status. Identify which devices must exchange signals and provide sequence-of-operation notes for normal conditions and relevant fault locations.

Also clarify switchboard dimensions or space constraints, incoming and outgoing cable entry, termination requirements, control-power expectations, metering or communications interfaces, and project submittal needs. These details help determine whether the requested ZSI arrangement fits the proposed assembly and what engineering review remains. Exact scope, component availability and production timing are confirmed for each order; do not treat a preliminary quote as approval of protection settings or a completed coordination design.

Review, delivery and project handoff

For Georgia projects, delivery planning should align the switchboard arrival with site readiness, receiving access, unloading capability and the installation sequence. Confirm the delivery location, schedule requirements and any site-specific handling constraints during procurement. Nationwide shipping can support projects across Georgia, but routing and timing depend on the confirmed order and shipment plan. Installation, wiring checks, testing and energization belong to qualified personnel following approved project documents and equipment instructions.

Before release, have the responsible engineer review the device schedule, ZSI signal relationships, terminal documentation and approved coordination settings. At handoff, provide the final drawings and device information needed by the installation and commissioning teams, and identify any field connections that must be completed or verified. To move forward, send the one-line diagram, fault-current and coordination information, breaker preferences, signal scheme and Georgia delivery requirements so the proposed new switchboard can be evaluated against the project’s protection goals.

Planning reference

Project specifications

Specifications are confirmed for each order
ScopeRequested by quote
VoltageBased on project requirements
CurrentSpecified to order
ListingDependent on the applicable assembly. UL 891 applies to applicable low-voltage switchboard assemblies, not medium- or high-voltage equipment.