Water utility engineers, contractors, and purchasing teams modernizing Georgia pump stations need switchgear plans that account for motors, standby power, telemetry, and uninterrupted service. Define how existing equipment operates before selecting a replacement configuration. A clear scope helps coordinate design, procurement, outage planning, and delivery while leaving final ratings and interfaces to project engineering review.

Made in USAUL 891 switchboard assemblies — low voltage onlyAccelerated lead times — confirm availability
Project-specific

Define the application and requirements.

Built in the USA

Discuss equipment and assembly options.

Schedule-aware

Confirm lead times for your order.

Start with the station’s operating sequence

Document each pump’s motor data, starting method, normal duty, and standby role. Record how pumps are staged, what conditions trigger alternation, and whether operators can run equipment locally when supervisory communications are unavailable. These details affect control compartments, feeder arrangements, and the signals needed at the switchgear boundary.

Gather existing one-lines, control schematics, equipment nameplates, and field observations, noting discrepancies rather than assuming old drawings are current. Identify available fault-current information, system voltage, grounding method, and upstream protective devices for engineering review. Confirm which loads must remain available during maintenance or a utility interruption, including controls and station auxiliaries.

Coordinate motor control and protection

For every motor feeder, establish the required disconnecting and protective functions and the intended starting approach. Across-the-line, reduced-voltage, and drive-based starts have different effects on inrush, feeder sizing, heat, and control interfaces. Share motor horsepower, full-load current, starting requirements, operating frequency, and any existing drive or starter data so the design team can evaluate the arrangement.

Also identify operating modes, interlocks, permissives, alarm contacts, and local control requirements. Pump alternation, dry-run protection, pressure or level inputs, and emergency operating logic may be handled outside the switchboard; define where each function resides and which interface points the assembly must provide. Final protection settings and equipment ratings require engineering coordination with the station system and applicable authority review.

Make backup power interfaces explicit

Describe the standby source, its electrical characteristics, and how the station transfers between normal and backup power. The switchgear scope may need to coordinate with transfer equipment, generator output protection, load sequencing, and provisions for load shedding. Clarify which pumps and auxiliary loads are expected to operate on backup power and whether simultaneous starting is intended.

Generator capacity alone does not establish the correct switchgear configuration. Review available fault current from each source, source grounding, transfer arrangement, neutral treatment, and the protective-device coordination approach. Identify any existing transfer equipment that will remain, be replaced, or be supplied under another contract. This division of work helps avoid gaps between switchboard, generator, and controls packages.

Define telemetry boundaries and handoff

List the information operators need remotely, such as pump run status, trip indication, source status, alarms, and selected electrical measurements. Specify the destination system and its interface expectations, including discrete contacts, communications protocol, network responsibilities, and whether the telemetry contractor provides gateways or field wiring. Confirm signal names and ownership before control drawings are finalized.

Telemetry requirements should not be inferred from a general request for remote monitoring. Identify which values originate in protective devices, motor controls, instruments, or the station PLC, and who configures and tests each path. The equipment package can be scoped around agreed interface points, but integration with the utility’s supervisory system requires coordinated documentation and project-specific testing responsibilities.

Plan phased replacement around service continuity

At an operating station, replacement sequence can be as important as the final lineup. Map existing feeders, temporary-power options, bypass arrangements, available outage windows, and the consequences of taking each pump out of service. Decide whether work will proceed by section, feeder, or a larger planned shutdown, and coordinate temporary connections and cutover procedures with qualified project personnel.

Compare the existing footprint, cable entry, conduit locations, access path, and room constraints with the proposed assembly. A new lineup may require changes to cable routing or field connections even when electrical functions are similar. For phased work, establish which legacy equipment stays energized between stages, what interfaces must be preserved, and how drawings and labels will reflect each cutover.

Prepare a quote and delivery plan

For a useful quote, provide the one-line diagram, system voltage, available fault-current study or known value, motor schedule, desired starter types, backup-source details, telemetry interface list, and photos or dimensions of the equipment space. Include the intended phasing, requested accessories, project schedule, and any division of responsibility among the switchgear, generator, transfer, and controls packages. Scope, component availability, and delivery timing are confirmed for each order.

For Georgia projects, coordinate the ship-to location, receiving hours, unloading arrangements, and the date the equipment must reach the site relative to outage and installation planning. Nationwide shipping can support utility projects across the state, but routing and timing depend on the order and shipment details. Before release, align approved drawings, interface schedules, and the cutover plan; then use those documents to coordinate installation, testing, and operator handoff.

Planning reference

Project specifications

Specifications are confirmed for each order
ScopeRequested by quote
VoltageBased on project requirements
CurrentSpecified to order
ListingDependent on the applicable assembly. UL 891 applies to applicable low-voltage switchboard assemblies, not medium- or high-voltage equipment.