Voltage dips, waveform distortion and demanding motor starts can disrupt production, but each calls for a different response. Georgia plant engineers and purchasing teams can use event monitoring and load data to identify what is happening before selecting corrective equipment. This guide outlines the measurements, operating details and project information that help shape a practical specification.

Made in USAUL 891 switchboard assemblies — low voltage onlyAccelerated lead times — confirm availability
Project-specific

Define the application and requirements.

Built in the USA

Discuss equipment and assembly options.

Schedule-aware

Confirm lead times for your order.

Start with the event, not the remedy

A machine trip or control reset is a symptom, not a diagnosis. Record when the event occurred, which loads were running, what equipment was affected and whether the disturbance coincided with a utility interruption, a large motor start, a process change or a switching operation. Production logs and operator observations add context that a meter reading alone may not provide.

Use power-quality instruments suited to the question and have qualified personnel install and interpret them. Capture voltage and current over representative operating periods, including normal production cycles, shift changes and infrequent high-load operations. Note instrument location, connection method, sampling capabilities and time synchronization so readings from different panels or plant systems can be compared meaningfully.

Measure voltage events in context

For voltage sags, swells and interruptions, document magnitude, duration, affected phases and location in the distribution system. Compare readings at the service entrance with measurements near sensitive drives, control panels or process equipment. A disturbance present throughout the plant points toward a different investigation than one confined to a branch circuit or load connection.

Ask which equipment actually stopped, what its undervoltage or ride-through limits are, and whether protection settings or control logic recorded an event. Distinguish a brief sag from a sustained low-voltage condition, and check for phase imbalance or loose connections through an appropriate electrical assessment. Corrective choices depend on event severity, frequency, source and the tolerance of the affected process.

Separate harmonics from ordinary load changes

Variable-frequency drives, rectifiers, welders and other nonlinear loads can draw current that distorts voltage waveforms. Measure harmonic current and voltage at relevant points, and identify which loads were operating during each capture. Total harmonic distortion is useful, but individual harmonic orders, phase relationships and system loading help engineers understand whether a particular source or resonance may be involved.

Before specifying filters or other mitigation, gather transformer and feeder information, capacitor-bank details, generator operating plans and the connection points of nonlinear loads. Existing capacitors can interact with system impedance, while a solution suitable for one operating state may perform differently as production loads change. Engineering review should establish the study assumptions, applicable limits and the equipment’s intended operating range.

Characterize motor-starting effects

Record motor nameplate data, starter type, start frequency, acceleration time and the driven process. Across-the-line starts can create substantial current and voltage drop; soft starters and drives alter the starting profile but bring their own settings, harmonics, bypass arrangements or operating constraints. Confirm whether the concern is a plant-wide dip, nuisance tripping, slow acceleration or a local mechanical issue.

A useful study needs the source and path of the starting current: utility or generator source, transformer size and impedance, feeder length and conductor information, and the motor’s location relative to sensitive loads. Consider simultaneous starts, restart sequences after an outage and the minimum voltage required by controls and contactors. Do not select a larger transformer, starter or compensation device on motor horsepower alone; verify the complete system response.

Turn measurements into a buildable specification

Share one-line diagrams, available fault-current information, existing switchboard and switchgear details, metering records, load schedules and photographs of nameplates or equipment labels. Include the monitoring dates, operating state, event logs, affected processes and the corrective options already considered. Identify whether the project is a new distribution assembly, a replacement, an added section or a change that must fit an existing lineup.

For a manufacturer quote, specify the intended function, system voltage and phase, bus and feeder requirements, enclosure and installation conditions, metering or communications needs, and any required interfaces with existing equipment. Provide drawing and submittal expectations, procurement milestones and the preferred delivery location in Georgia. Scope, component availability, configuration and schedule are confirmed for each order; UL 891 applies to switchboard assemblies, not as a blanket certification for medium- or high-voltage switchgear.

Coordinate delivery with the plant plan

A measured diagnosis helps purchasing compare solutions on function rather than a generic label such as power-factor correction or harmonic filter. Have the engineer identify required performance, operating cases, protection coordination and any upstream or downstream modifications. Review how the proposed assembly will connect to existing equipment, what shutdown window is needed and which party is responsible for field verification, installation and commissioning.

Before releasing the order, align approved drawings, connection details, site access, receiving arrangements and the installation sequence among engineering, facilities, the electrical contractor and procurement. Georgia delivery can be coordinated to the project destination, with shipping and timing confirmed for the specific order. The actionable next step is to assemble representative event captures, motor-start data and distribution drawings, then request a configuration review against the documented plant conditions.

Planning reference

Project specifications

Specifications are confirmed for each order
ScopeRequested by quote
VoltageBased on project requirements
CurrentSpecified to order
ListingDependent on the applicable assembly. UL 891 applies to applicable low-voltage switchboard assemblies, not medium- or high-voltage equipment.