Incident Energy Labels

Incident energy labels give qualified electrical workers equipment-specific information for assessing arc-flash exposure before work begins. For Georgia facilities, the label is useful only when its calculations reflect the actual system configuration and protective-device settings. This guide explains what the label represents, when reassessment is warranted, and what to coordinate when new switchgear is specified.

Made in USAUL 891 switchboard assemblies — low voltage onlyAccelerated lead times — confirm availability
Project-specific

Define the application and requirements.

Built in the USA

Discuss equipment and assembly options.

Schedule-aware

Confirm lead times for your order.

What a calculated label tells the worker

An incident energy label summarizes results from an arc-flash risk assessment for a defined point in an electrical system. Depending on the assessment and applicable requirements, it may identify nominal system voltage, calculated incident energy at a stated working distance, the arc-flash boundary, and the assessment date. The information helps qualified personnel evaluate exposure and plan work; it does not replace an energized-work risk assessment, safe work practices, or the employer’s electrical safety program.

The number is a calculation, not an intrinsic property of a switchboard or switchgear lineup. It depends on the modeled fault current, protective-device clearing time, equipment configuration, enclosure characteristics, and assumptions such as working distance. A label without a clear connection to the study, equipment location, and modeled operating condition can be difficult to apply correctly. Facilities teams should maintain the study and label information together.

Why the installed system matters

Incident energy can change when the source, transformer, conductor path, or protective device changes. A utility service modification, generator addition, transformer replacement, tie arrangement, or altered feeder can affect available fault current and the time required for a device to clear a fault. More fault current does not automatically mean more incident energy: a protective device may operate faster or slower in different parts of its curve. The result requires engineering analysis of the actual system.

Operating configuration matters as well. A normally open tie that is closed, parallel sources, alternate generator operation, or a maintenance setting can produce a different result from the normal configuration. If a study evaluates multiple operating modes, the project team should establish how the modes are identified and how workers can determine which label information applies. Do not assume a single value covers every possible configuration.

Settings and equipment changes to track

Protective-device settings are a frequent reason to revisit calculated values. Changes to instantaneous pickup, short-time pickup or delay, ground-fault functions, or maintenance-mode settings may alter clearing time. Replacement breakers and trip units can also have different characteristics, even when their frame size or nominal rating appears similar. Record approved settings and confirm that installed devices match the assumptions used in the assessment.

Other triggers include changes to conductor length or size, transformer impedance, source contribution, switchboard or switchgear construction, and the addition or removal of protective devices. Maintenance findings can also reveal that the as-built system differs from the one studied. Not every change requires an entirely new study, but an engineer should determine whether the model remains representative and whether affected labels need revision.

Specify equipment with the assessment in mind

When purchasing new switchgear or a UL 891 switchboard assembly, share the project’s available one-line diagram, system voltage, source and transformer data, fault-current information, protective-device schedule, and intended operating modes. Identify the equipment location and the interfaces with existing feeders, ties, and upstream devices. If final utility data or settings are pending, identify those items as open assumptions rather than treating preliminary values as confirmed.

Discuss who will perform or update the arc-flash assessment, provide device-setting coordination, and prepare the final labels. Confirm what equipment data will be supplied for that work, including device models and trip-unit details where applicable. UL 891 applies to switchboard assemblies; it does not establish an incident-energy result or provide blanket coverage for medium- or high-voltage equipment. Scope, configuration, availability, and delivery timing are confirmed for each order.

Coordinate handoff and Georgia delivery

A useful handoff links each label to the equipment name or identifier used in the one-line diagram and study. Before energization, the project team should reconcile installed equipment and settings with the final documentation, resolve deviations, and confirm that labels correspond to the assessed configuration. Provide the facilities team with the study basis, device-setting records, and a process for reviewing future changes so a label does not remain in service after its assumptions have changed.

For Georgia projects, coordinate the shipping destination, receiving access, delivery sequence, and any site-specific handling or scheduling constraints while the equipment configuration is being finalized. Nationwide shipping can support projects across the state, but delivery dates and order scope are confirmed for the specific project. Before requesting a quote, share the one-line diagram, equipment type and location, system and source data, protective-device requirements, known operating modes, target delivery point, and any unresolved engineering assumptions.

Planning reference

Project specifications

Specifications are confirmed for each order
ScopeRequested by quote
VoltageBased on project requirements
CurrentSpecified to order
ListingDependent on the applicable assembly. UL 891 applies to applicable low-voltage switchboard assemblies, not medium- or high-voltage equipment.