New electrical distribution equipment, built around your projectServing Georgia
Gray electrical switchgear cabinets on wooden pallets, viewed at an angle.

Configurations

Generator Paralleling Switchgear

Generator paralleling switchgear coordinates multiple generator sources so they can connect to a common bus and support facility loads. Georgia engineers, contractors and facility teams can use this page to define source operation, load-sharing needs, controls, protection and project interfaces before requesting a manufacturer-built configuration.

Made in USAUL 891 switchboard assemblies — low voltage onlyAccelerated lead times — confirm availability
Project-specific

Define the application and requirements.

Built in the USA

Discuss equipment and assembly options.

Schedule-aware

Confirm lead times for your order.

Define how the generator sources will operate

Start with the intended operating sequence. Generators may start together to serve a planned load, start in stages as demand rises, or operate in standby arrangements where a utility interruption initiates a defined transfer sequence. The required sequence affects breaker arrangement, control logic, interlocks and the information operators need at the switchgear. Describe normal, emergency and test modes rather than relying on a general statement that the generators will run in parallel.

Provide the generator count, each unit’s nameplate data, output voltage and frequency, and whether the units are identical or differ in capacity or controls. Explain which sources may operate together and whether the system must accommodate a unit unavailable for maintenance. These details help establish the bus arrangement and identify operating cases for engineering review; they do not, by themselves, determine a final rating or approve a design.

Specify synchronization and breaker control

Before a generator breaker closes onto an energized bus, the control scheme must establish that the source is suitable for connection. The project specification should identify the intended synchronization method and the signals or equipment available from each generator controller. Relevant considerations include voltage, frequency, phase relationship, breaker status and the sequence for permissive, close and post-close control. Confirm who supplies each function and where control responsibility passes between generator packages and paralleling gear.

Clarify whether the bus is normally dead before the first generator closes, remains energized by another source, or can be energized under more than one operating condition. Also document manual and automatic operating expectations, local versus remote commands, and what should happen after a failed start or unsuccessful synchronization attempt. These operating details let the manufacturer coordinate control interfaces without assuming a specific generator make, controller or project sequence.

Plan load sharing and load management

When multiple generators share a bus, specify how active and reactive load should be distributed and whether the units should share proportionally to their capacity. The answer can depend on generator controls, communications, plant operating goals and the range of units expected to run together. Identify any required load-management functions, such as starting additional units as demand increases, shedding selected loads when capacity is limited, or restoring loads in stages after a source becomes available.

List major loads and their operating behavior, including large motor starts, variable-frequency drives, sensitive electronic loads and any loads that cannot tolerate interruption. Share the expected demand profile and the priority of essential versus deferrable loads. The engineering team can use this information to coordinate the proposed control scope and review the system’s operating cases. Actual performance depends on the complete generation and distribution design, not switchgear alone.

Coordinate protection and system interfaces

Protection must account for generator sources operating together, the paralleling bus and downstream distribution. Provide available generator protection information, fault-current and coordination studies when available, and the project’s intended protection philosophy. Identify required protective functions and which party is responsible for relays, settings, current transformers, voltage sensing, trip circuits and coordination with generator packages. Final device selection and settings require engineering based on the actual system and applicable review.

Map the interfaces to utility service, transfer equipment, downstream switchboards, building controls, emergency systems and remote monitoring. For each connection, identify the source of status and command signals, communications expectations, cable or terminal responsibilities, and any required alarm points. A clear interface schedule can expose scope gaps early, especially where the generator supplier, electrical contractor and switchgear manufacturer divide responsibilities.

Resolve ratings, construction and procurement inputs

For a quote, share the one-line diagram, generator schedules, system voltage, frequency, available fault-current information, bus requirements, enclosure and installation conditions, and the required delivery destination in Georgia. Include project specifications, control narratives, preferred equipment arrangement and any preliminary studies. If some documents are not complete, identify what is known, what remains open and who will provide the missing information. Exact configuration, availability and timeline are confirmed for each order.

Ask how the proposed assembly will accommodate the required generator breakers, metering, controls, protection and field connections, and identify any dimensions or access constraints that affect the electrical room. UL 891 applies to switchboard assemblies; it is not a blanket listing for medium- or high-voltage switchgear. The applicable construction and certification scope must be established for the actual equipment and project requirements rather than inferred from a general product description.

Carry the sequence through delivery and startup

A useful project handoff includes approved drawings, control narratives, interface schedules, equipment data and a sequence of operation that the generator supplier and installing contractor can review. Set expectations for drawing review, changes, factory documentation and the information needed before release to production. Georgia delivery should be coordinated with the site’s receiving access, unloading plan, installation sequence and construction schedule; shipping arrangements and timing depend on the specific order.

Before requesting a quote, assemble the generator data, one-line, operating sequence, load priorities, protection requirements and delivery location, then note unresolved decisions and responsible parties. This gives the manufacturer a practical basis to scope custom-built paralleling switchgear and identify coordination needs. Final design, installation, settings and commissioning should be completed by qualified professionals with the required engineering and authority reviews.

Planning reference

Project specifications

Specifications are confirmed for each order
ScopeRequested by quote
VoltageBased on project requirements
CurrentSpecified to order
ListingDependent on the applicable assembly. UL 891 applies to applicable low-voltage switchboard assemblies, not medium- or high-voltage equipment.
Request a Quote