New electrical distribution equipment, built around your projectServing Georgia
Rows of gray electrical switchgear cabinets on pallets in a large indoor space.

Voltage

120/208-Volt Switchgear Specifications

For Georgia engineers, electrical contractors and facility teams, specifying 120/208-volt three-phase wye switchgear starts with matching the assembly to the source, loads and distribution plan. Clarify whether the system needs a full neutral, how branch and three-phase loads will be served, and which ratings the project requires before requesting a manufacturer quote.

Made in USAUL 891 switchboard assemblies — low voltage onlyAccelerated lead times — confirm availability
Project-specific

Define the application and requirements.

Built in the USA

Discuss equipment and assembly options.

Schedule-aware

Confirm lead times for your order.

Confirm the system configuration

A 120/208-volt, three-phase, four-wire wye system provides 208 volts between phases and 120 volts from any phase to neutral. Confirm that this is the intended source configuration, not a 120/240-volt single-phase service or a different three-phase voltage. Provide the source and grounding details, available fault-current information, and the project’s nominal voltage so the proposed assembly can be evaluated against the actual distribution system.

Identify the point where the switchgear will connect and whether the equipment is service entrance or downstream distribution. That distinction affects the intended arrangement and specifications. Share the one-line diagram, service or feeder conductors, and any project requirements for main and feeder devices. Final design, ratings and installation details require review by the responsible electrical engineer and the authority having jurisdiction.

Decide what the neutral must serve

The neutral is central to a 120/208-volt wye system when the distribution includes line-to-neutral loads such as lighting, receptacles, controls or other 120-volt equipment. State whether the switchboard needs a neutral bus, how neutral conductors will terminate, and whether the project documents specify a full-capacity neutral or another engineered arrangement. Do not assume a reduced neutral is suitable simply because some loads are three-phase.

Describe expected load balance and any nonlinear loads, including electronic power supplies, LED drivers, computers or variable-frequency drives. Their neutral-current effects depend on the equipment and the load mix. Provide the engineer’s neutral sizing criteria and any monitoring or metering requirements. The manufacturer can use the approved design inputs to develop the assembly configuration; the project engineer determines the required conductor and bus capacities.

Map connected loads and distribution

Provide a load schedule that separates 120-volt, 208-volt single-phase and 208-volt three-phase loads. Include connected load, anticipated demand, motor or equipment starting information where relevant, and planned spare capacity. Identify critical loads, future additions and any loads that need dedicated feeders. This information helps establish the number and arrangement of feeder devices, bus requirements and space needs without assuming that every circuit will be fully loaded at once.

Phase assignment matters where many 120-volt circuits share a three-phase source. Share the intended phase distribution or the design criteria for balancing, along with panel or downstream distribution relationships. If the project includes large motors, heating equipment or sensitive loads, identify them rather than relying only on a total kVA figure. The responsible engineer should confirm calculations and coordinate the switchboard schedule with the complete electrical design.

Specify ratings and physical details

State the required continuous-current rating, short-circuit or withstand requirements, and protective-device characteristics from the project documents. Available fault current and upstream protection are essential inputs; voltage alone does not establish an adequate interrupting or withstand rating. Also identify the required main-device type, feeder device types, metering, control power and any specified accessories. UL 891 applies to switchboard assemblies; it is not a blanket listing for medium- or high-voltage switchgear, and the applicable assembly scope must be confirmed for the order.

Provide the installation environment and dimensional constraints, including indoor or outdoor application, room access, working clearances, cable entry direction and conductor space. Share the required enclosure and construction details from the design, plus any seismic or other project criteria that apply. Custom-built configurations can be developed around approved requirements, but exact scope, component availability and production timing are confirmed for each order rather than inferred from a standard voltage description.

Prepare a useful quote and delivery handoff

For a quote, send the one-line diagram, load and feeder schedules, source and grounding data, available fault-current study, required ratings, preferred device arrangement and installation dimensions. Note the project stage, required submittal information, requested ship-to location in Georgia and site access or receiving constraints. Flag open engineering decisions clearly; documenting assumptions helps the manufacturer identify what must be resolved before the configuration is finalized.

Georgia delivery should be coordinated with the construction schedule, receiving hours, unloading plan and the electrical room’s access route. Nationwide shipping is available, while the exact shipping arrangement and timing depend on the order and destination. Before release, align the approved drawings, equipment schedule and delivery details among the engineer, contractor, facility team and purchasing manager. To begin, assemble the system data and load documents, then request a configuration and quote based on those project-specific inputs.

Planning reference

Project specifications

Specifications are confirmed for each order
ScopeRequested by quote
VoltageBased on project requirements
CurrentSpecified to order
ListingDependent on the applicable assembly. UL 891 applies to applicable low-voltage switchboard assemblies, not medium- or high-voltage equipment.
Request a Quote