New electrical distribution equipment, built around your projectServing Georgia
Three gray electrical switchgear cabinets on pallets, with a door swung open.

Voltage

347/600-Volt Switchgear Specifications

For Georgia engineers, contractors, facility teams, and purchasing managers, specifying 347/600-volt wye switchgear starts with confirming how the system is grounded, what the equipment must serve, and which ratings apply to every component. We build new switchgear to project requirements and review the intended application, applicable codes, and component availability before finalizing a configuration.

Made in USAUL 891 switchboard assemblies — low voltage onlyAccelerated lead times — confirm availability
Project-specific

Define the application and requirements.

Built in the USA

Discuss equipment and assembly options.

Schedule-aware

Confirm lead times for your order.

Confirm the system voltage and grounding

A 347/600-volt designation describes a wye system with 600 volts between phases and 347 volts from phase to neutral. Confirm that this matches the facility’s actual electrical service and the intended distribution arrangement. A voltage label alone does not establish neutral availability, grounding method, or suitability for a particular load.

Share the service point, source characteristics, grounding arrangement, and whether the switchgear must distribute a neutral. Identify any required neutral bus provisions and connections to the grounding system. The project engineer should establish these details from utility information and approved design documents, rather than infer them from equipment used elsewhere in the facility.

Specify ratings by component

Request and review the ratings that apply to the complete assembly and its individual devices. These may include system voltage, continuous current, short-circuit or interrupting capability, and the withstand rating of the assembled equipment. Breaker ratings, bus ratings, and assembly ratings are related but are not interchangeable; the available combinations depend on the design and selected components.

Provide the available fault-current information and the protection study or coordination requirements when established. Confirm device type, trip functions, pole configuration, and any required neutral switching against the one-line diagram. A component’s nameplate rating does not by itself establish the rating of the assembled switchgear, so the approved configuration must be checked as a whole.

Resolve code and approval requirements

Identify the codes and editions applicable to the project, the jurisdiction having authority, and any owner or utility criteria. Requirements can vary with the installation and project documents. Engineering review and the authority having jurisdiction must determine whether the proposed arrangement is acceptable; do not assume a voltage designation resolves code questions or establishes compliance.

For switchboard assemblies specified to UL 891, confirm that the requested product scope and configuration fall within the applicable standard and evaluation. UL 891 applies to switchboards; it is not a blanket listing for medium- or high-voltage switchgear. Describe the equipment accurately in drawings, schedules, and procurement documents, and identify any separate equipment standards or approvals required by the project.

Match the lineup to the distribution plan

The one-line diagram should show incoming service, bus arrangement, feeder quantities, load destinations, and protective devices. Note whether the design calls for main-tie-main sections, metering, bypass provisions, or future feeder spaces. For 347/600-volt systems, clarify which loads use phase-to-neutral voltage and which use phase-to-phase voltage, and coordinate neutral and grounding details throughout the lineup.

Provide available room dimensions, access and working-space constraints, cable entry direction, conduit locations, and any restrictions on moving equipment into the electrical room. Identify environmental conditions and whether special enclosures or construction are needed. These details shape a buildable configuration, but final dimensions and installation clearances must be reviewed by the project’s qualified design and installation team.

Plan procurement around confirmed availability

American-made components and custom-built configurations can support a project’s sourcing and design goals, but a requested device, accessory, or rating may not be available in every combination. Provide acceptable alternates only when the engineer and owner can evaluate them. We confirm component availability, scope, and schedule for each order rather than treating a general lead-time expectation as a commitment.

For a useful quotation, share the one-line diagram, equipment schedule, required standards, component and assembly ratings, feeder list, control or metering needs, enclosure details, and requested delivery location in Georgia. Include drawing-review milestones and any required submittal documents. The more completely the package defines the design, the more directly the proposed configuration can be checked against the project requirements.

Coordinate submittals and Georgia delivery

Before release for construction, compare approved submittal drawings with the one-line, schedules, and site constraints. Resolve differences in bus arrangement, neutral treatment, breaker functions, metering, and incoming or outgoing connections in writing. Confirm what the order includes, what remains by others, and which revisions require renewed engineering review.

Share the Georgia delivery address, site access limitations, receiving hours, unloading arrangements, and required delivery sequence when requesting a quote. Nationwide shipping is available, with timing and logistics confirmed for the order. Before procurement, assemble the verified system voltage and grounding data, fault-current basis, governing requirements, approved drawings, and delivery plan so the specified 347/600-volt equipment can be evaluated and coordinated for the actual project.

Planning reference

Project specifications

Specifications are confirmed for each order
ScopeRequested by quote
VoltageBased on project requirements
CurrentSpecified to order
ListingDependent on the applicable assembly. UL 891 applies to applicable low-voltage switchboard assemblies, not medium- or high-voltage equipment.
Request a Quote